 S/BIP/SCB965300/A/13/01/2003
page 1 / 3 F/GB
Relais Statique Double Double Solid State Relay
* Sortie AC synchrone : 24-600Vac-50A x 2 . * Une Commande pour 2 voies. * Connection de Puissance et de Commande par vis. * Possibilite de protection IP00 en option:Capot 1K470 000. * 24-600VAC -50A x 2 Zero-Cross AC Output. * One Control for 2 legs. * Power and Control connections by screw therminal. * Protection IP00 optional (1K470 000).
SCB965300
10-30 VDC control 50A/600VAC output
Application typique/Typical application
L1
3 phases 200 up to 480VAC L1 L2 L3
+
1 input output T1 L2
Y wiring
wiring
2
-
input
output T2
single phase
Caracteristiques de commande (a 20C) / Control characteristics (at 20C) Parameter Tension de commande / Control voltage Courant de commande / Control current (@ Uc nom ) Tension de relachement/Release voltage Resistance interne / Input internal resistor fig.1 Tension inverse / Reverse voltage Symbol Uc Ic Uc off Rc Urv Min 10 5 1 DC Nom Max 30 Unit V mA V V V V V
fig. 1 :Caracteristique d'entree / Control characteristic
30 27 24 21 18 15 12 9 6 3 0 0 5 10 15 20 25 30 35
1000 30
Caracteristiques d'entree-sortie (a 20C) / Input-output characteristics (at 20C) Isolement entree-sortie/Input-output isolation @500m Uimp/Ui 4000/3300 Isolement sortie-semelle/Output-case isolation @500m Uimp/Ui 4000/3300 Isolement entre voies / Leg 1-Leg 2 isolation @500m Uimp/Ui 4000/3300 Caracteristiques generales / General characteristics Parameter Poids/Weight Plage de temperature de stockage / Storage temprange Plage de temperature de fonctionnement/Operating temprange Resistance thermique Jonction-Case/Junct.-Case thermal resistance(1 leg) Conditions
Ic (mA)
Uc (V)
Symbol
Typ. 110 -40/+100 -40/+100 0,6
Unit g C C C/W
Proud to serve you
All technical caracteristics are subject to change without previous notice. Caracteristiques sujettes a modifications sans preavis.
celduc
r e l a i
s
S/BIP/SCB965300/A/13/01/2003
page 2 / 3 F/GB
Caracteristiques de sortie(a 20C) / Output characteristics (at 20C) Parameter Tension de charge / Load voltage Plage tension de fonctionnement / Operating range Tension crete (ecreteur de tension) / Peak voltage (clamping voltage) Niveau de synchonisation / Synchronizing level Tension d'amorcage / Latching voltage Courant nominal AC1/ AC1 nominal current Courant de surcharge non repetitif /Non repetitive overload current Chute tension directe crete/ On state voltage drop Courant de fuite etat bloque/ Off state leakage current Courant de charge minimum / Minimum load current Temps de fermeture/ Turn on time Temps d'ouverture/ Turn off time Plage de frequence / Operating frequency range dv/dt etat bloque / Off state dv/dt dI/dt maximum non repetitif/ Maximum di/dt non repetitive I2t (<10ms) Possibil!te de protection exterieure / External protection possibilty Symbol Ul Ulmin-max Up Usync Il nom Ua ( see Fig. 2 ) Il AC1 tp=10ms (Fig. 3) Itsm @ Il nom Vd @Ul, 50Hz Ilk Ilmin Uc nom DC ,f=50Hz ton max Uc nom DC ,f=50Hz toff max f dv/dt di/dt I2t Conditions Typ. Unit 400 V rms 24-600 V rms 1200 V 50 V 5 V 50 A rms 550 A 1,6 V 1 mA 5 mA 10 ms 10 ms 10-440 Hz 500 V/s 50 A/s 1500 A2s fusible/ fuse
Fig.2 Courbes thermiques /Thermal characteristics
Fig.2 Courbes thermiques /Thermal characteristics
Relais double: 50A/ itsm=550A
160 0,3K/W
45
140
40
120
2 ways
Courant par voie / Current by leg (A)
0,75K/W
WF115000 (0,9C/W) 35 30 WF131100 (1,1C/W) 25 20 15 1LW27100(2,7C/W) 10 ON A PLATE(4C/W) 5 1LW23100/WF262100 (2,2C/W)
0,95K/W 100 Total dissipated power (W)
80 1,6K/W 60 1 way 2,2K/W 40 6K/W
20
0 0
WITHOUT HEATSINK(12C/W) 10 20 30 40 50 60 70 80 90 100
0 0 5 10 15 20 25 30 35 40 45 50 0 10 20 30 40 50 60 70 80 90 100
Temperature ambiante /Ambiant temperature (C)
RMS load current (A)
Ambient temperature (C)
Fig.3 Courbes de surcharge de courant / Overload current curves
Surge current Itsm (A peak) = f(t) Itsm (Apeak) 600 400 for models with Itsm =550A
1 -Itsm non repetitif sans tension reappliquee est donne pour la determination des protections. No repetitive Itsm is given without voltage reapplied for the determination of the protection. 2 -Itsm repetitif est donne pour des surcharges de courant (Tj initiale=70C). La repetition de ces surcharges de courant diminue la duree de vie du Relais. Repetitive Itsm is given for inrush current with initial Tj = 70C. The repetition of the surge current decrease the lifetime SSR's .
200
0 0,01
0,1
t (s)
11
10
Proud to serve you
All technical caracteristics are subject to change without previous notice. Caracteristiques sujettes a modifications sans preavis.
celduc
r e l a i
s
S/BIP/SCB965300/A/13/01/2003
Caracteristiques mecaniques /Mechanical specifications
27 22,4 19,6 44,5 28 O 4,7 27 M4 22,4 19,6
page 3 / 3 F/GB
=
celduc
L1 L2
9907194L8
10,2
47,6
50A
50A
10,2
42,5
T1
=
(24-600Vac) Input
400Vac
+
10-30 Vdc
T2 (24-600Vac)
400Vac
SCB865300 with heatsink
7,75
16 max
5,2
58
I
16 max
-Nde lot :9906173 Suivi du -Date code :L6 (juin 99) -Batch number : 9906173 following of -Manufacture date : L6 ( june 99)
Sorties / Outputs
Vis / screws : : M4 1,8 Nm
Entrees / Inputs
Section max de fil / Max. wire Screwdriver type : Couple de serrage /Screws torque : : 12 AWG 2,5 mm2 3,5 x0,5 mm 0,4 Nm
Couple de serrage / Screws torque
Tableau de sections de fil pour la gamme SC (Exemples) / Wiring tabs for the outputs SC range (exemples)
I max (A) Fil / wire (mm2) AWG/ MCM
L W W
L=22mm W=8,5mm <20 25 32 2,5 4 6 12 10 10 AMP : 0-0034160-0 L=27mm W=7mm AMP : 0-0034853-0 L=27mm W=7mm AMP : 0-0034853-0 L=23,7mm W=11,9mm AMP : 0-0032996-0
L=20mm W=6mm AMP : 0-0165012-1 L=31mm W=8mm AMP : 0-0132269-1 L=31mm W=8mm AMP : 0-0132269-1 x
Fils d'entree / Input wires
60,5 mm
50
10
8
Precautions : * Les relais a semiconducteurs ne procurent pas d'isolation galvanique entre le reseau et la charge.
Cautions : * Semiconductor relays don't provide any galvanic insulation between the load and the mains.
celduc
r e l a i s
www.celduc.com
Rue Ampere B.P. 4 42290 SORBIERS - FRANCE E-Mail : celduc-relais@celduc.com Fax +33 (0) 4 77 53 85 51 Service Commercial France Tel. : +33 (0) 4 77 53 90 20 Sales Dept.For Europe Tel. : +33 (0) 4 77 53 90 21 Sales Dept. Asia : Tel. +33 (0) 4 77 53 90 19


▲Up To Search▲   

 
Price & Availability of SCB965300

All Rights Reserved © IC-ON-LINE 2003 - 2022  

[Add Bookmark] [Contact Us] [Link exchange] [Privacy policy]
Mirror Sites :  [www.datasheet.hk]   [www.maxim4u.com]  [www.ic-on-line.cn] [www.ic-on-line.com] [www.ic-on-line.net] [www.alldatasheet.com.cn] [www.gdcy.com]  [www.gdcy.net]


 . . . . .
  We use cookies to deliver the best possible web experience and assist with our advertising efforts. By continuing to use this site, you consent to the use of cookies. For more information on cookies, please take a look at our Privacy Policy. X